3 Phase 3-Wire AC Voltage Transduce   ModelGS-AV3C1-x9MC

3 Phase 3-Wire AC Voltage Transduce ModelGS-AV3C1-x9MC

Model
GS-AV3C1-x9MC
Input Range
AC 0~500V
Power Supply
AC/DC 85V~265V
Output
DC 0-5V、0-10V、0-20mA、4-20mA
Mounting
35mm DIN Rail
Size
116(L)x25(W)x87mm(H)
3 Phase 3-Wire  AC Voltage Transducer,  Model:GS-AV3C1-x9MC

Overview


AV3B1 series product is a 3 Phase 3-wire  AC voltage transducer. It detects  AC volltages in  wires, and generates  signals proportional to those voltages. The generated signals could be analog voltage (0-5V or 0-10V) or current (0-20mA or 4-20mA). The generated signals can be then used to display the measured voltages in an ammeter, or can be stored for further analysis in a data acquisition system, or can be used for the purpose of control.


Specifications:
* Basic Accuracy:Class 0.5
* Power Supply:AC/DC 85-265V;
* Input Voltage Range:AC 0~500V
* Frequency Range:50~3000Hz
* Output Signal:0-5V、0-10V、0-20mA、4-20mA
* Operating Temperature:-10℃~+60℃
* Load Capacity of Output:Voltage output ≥2KΩ;Current Output ≤250Ω
* Static Power:≤0.5W
* Rated Power:≤1.5W
* Load of Insulation Voltage:DC 2500V
* Response Time:≤300ms
* Thermal Drift:≤300PPm/℃
* Lightening Surge:Power end 2000V,Input end 2000V,Output end 500V
* Case Style:M
* Case Material:ABS (flame retardant)
* Installation:35mm DIN rail.

Part Number Guides:

Inside the model GS-AV3C1-x9MC, "x" means "output". There are different output values for options.

For examples:

GS-AV3C1-A9MC:3 phase 3-wire ac voltage transducer,3 isolating,sine wave,output 0-5V,power supply 220Vac,case style M,accuracy:Class 0.5
GS-AV3C1-C9MC:3phase-3-wire ac voltage transducer.3 isolating,sine wave,output 0-20mA,power supply 220Vac,case style M,accuracy:Class 0.5
GS-AV3C1-D9MC:3 phase-3 wire ac voltage transducer,3 isolating,sine wave,output 4--20mA,power supply 220Vc,case style M,accuracy:Class 0.5

Wiring diagrame:

  wiring for power supply of  220V AC:
   
      
Terminals 4,5,and 6 are for  input; Terminals 7,8 and 9 are for signal output; Terminals 10 and 11 are for Power supply; Terminal 12 are GND for both signal output. Terminals 1,2 and 3 are NC (No Connection).