Single Phase AC Voltage Transducer Model:GS-AV1C1-x9MC

Single Phase AC Voltage Transducer Model:GS-AV1C1-x9MC

Model
GS-AV1C1-x9MC
Input Range
AC 0~1000V
Power Supply
AC/DC 85V~265V
Output
DC 0-5V、0-10V、0-20mA、4-20mA
Mounting
35mm DIN Rail
Size
116(L)x25(W)x87mm(H)
Single Phase AC Voltage Transducer    Model No.:GS-AV1C1-x9MC

AV1C1 series product is a single Phase AC voltage transducer. It detects  AC volltage in a wire, and generates a signal proportional to that voltage. The generated signal could be analog voltage (0-5V or 0-10V) or current (0-20mA or 4-20mA). The generated signal can be then used to display the measured voltage in an ammeter, or can be stored for further analysis in a data acquisition system, or can be used for the purpose of control.


Specifics:
* Basic Accuracy:Class 0.5 
* Power Supply:AC/DC 85-265V;
* Input Voltage Range:AC 0~1000V
*Input Frequency:50Hz
*Output Signal:0-5V、0-10V、0-20mA、4-20mA, (Optional)
*Operating Temperature:-10℃~+60℃
*Load of Output:Voltage Output ≥2KΩ;Current Output ≤250Ω
*Static Power:≤0.5W
*Rated Power:≤1.5W
*Load of Insulation Voltage:DC 2500V
*Response Time:≤300ms
*Thermal Drift:≤300PPm/℃
*Lightening Surge:Power end 2000V,Input end 2000V,Output end 500V
*Case Style:M
*Case Material:ABS(flame retardant)
*Installation:35mm DIN Rail.

Part Number Guides:

Inside the model GS-AV1C1-x9MC, "x" means "output". There are different output values for options.

For examples:

GS-AV1C1-A9MC  1 phase ac voltage transducer,3 isolating,sine wave,output 0-5V,power supply 220Vac,case style M,Accuracy:Class 0.5
GS-AV1C1-C9MC  1 phase ac voltage transducer.3isolating,sine wave,output 0-20mA,power supply 220Vac,case style S,accuracy:Class 0.5
GS-AV1C1-D9MC  1 phase ac voltage transducer,3 isolating,sine wave,output 4--20mA,power supply 220Vac,case style S,accuracy:Class 0.5


Wiring diagrame:

      Wiring for power supply of 220V AC:



Terminals 1 and 3 are for input;   Terminal 7 is for output; Terminals 10 and 11 are for power supply; Terminal 12 is GND,. Output and Power Supply don’t share GND.Terminals 2、4,5,6、8、and 9 are NC (No Connection);