Single Phase AC Voltage Transducer Model:GS-AVIB1-xxSC

Single Phase AC Voltage Transducer Model:GS-AVIB1-xxSC

Model
GS-AV1B1-xxSC
Input Range
AC 0--1000V
Power Supply
DC 12V15V24V;
Output
DC 0-5V0-10V0-20mA 4-20mA
Mounting
35mm DIN Rail or Screw
Size
Length:116mm; Width:25mm; Height:87mm;

Single Phase AC Voltage Transducer     GS-AV1B1-xxSC

Overview

GS-AVIB1-xxSC series is single Phase AC voltage transducer. It detects AC voltage in a live wire and generates a signal proportional to that measured voltage. The generated signal could be 0-5V DC,0-10VDC,0-20mA DC or 4-20mA DC; The generated signal can be connected to PLC,voltage meters,acquisition devices or industrial automation control system.


Specifications:
* Basic Accuracy:Class 0.5
* Power Supply:+12V、+15V、+24V.  (Optional)
* Input Voltage Range:AC 0~1000V
* Frequency:50Hz (default)
* Output Signal:0-5V、0-10V、0-20mA、4-20mA, (Optional)
* Ambient Temperature:-10℃~+60℃
* Load of Output:Voltage Output ≥2KΩ;Current Output ≤250Ω
* Static Power:≤0.3W
* Rated Power:≤0.7W
* Insulation Voltage:DC 2500V
* Response Time:≤300ms
* Thermal Drift:≤300PPm/℃
* Lightning Surge:Power end 2000V,Input end 2000V,Output end 500V
* Case Style:S
* Case Material:ABS(flame retardant, UL94-V0)
* Mounting:35mm DIN Rail.

Part Number Guides:
 
Inside the model NB-AV1B1-xxSC, "xx" means "output" and "power supply". There are different output values and power supplies for options. For examples:
NB-AV1B1-A4SC  Single phase ac voltage transducer,2 isolating,sine wave,output 0-5V,power supply 24V,case syle S,Accuracy :Class 0.5
NB-AV1B1-C2SC  Single phase ac voltage transducer.2isolating,sine wave,output 0-20mA,power supply 12V,case syle S,accuracy:Class 0.5
NB-AV1B1-D3SC  Single phase ac voltage transducer,2 isolating,sine wave,output 4--20mA,power supply 15V,case syle S,accuracy:Class 0.5


Wiring diagrame:
Wiring for power supply of 12V D ,15V DC,or 24V DC:

Terminals 1 and 3 are for input;Terminals 11 and 12 are for output; Terminals 10 and 11 are for power supply;Terminasl 11 is GND for both output and power supply.Terminals 2, 4, 5, 6, 7, 8 and 9 are NC (No Connection); 