AC Current Transducer

  • 0.5A~30A AC, Three Phase AC Current Off-limit Alarm Transducer
  • 0.5A~30A AC, Three Phase AC Current Off-limit Alarm Transducer
  • 0.5A~30A AC, Three Phase AC Current Off-limit Alarm Transducer
  • 0.5A~30A AC, Three Phase AC Current Off-limit Alarm Transducer

0.5A~30A AC, Three Phase AC Current Off-limit Alarm Transducer

contact us
share to:
  • Features
  • Download

Three Phase AC Current Off-limit Alarm Transducer,output switch value signal as Relay passive contact signal or Open collect signal..


Overview
This transducer Model GS-AI3C1-JxEC is a three phase AC current off-limit alarm transducer. It adopts high-precision isolation components to isolate the measured AC current signal and outputs switch value signal. The input signal is a single phase AC current  signal and the output signal is a relay passive contact switch (or OC gate). When the AC current exceeds the set upper limit value or lower limit value, it will output the over limit alarm signal or under limit alarm signal, and the output signal is the relay contact signal. Within the input range, the action limit value of AC current can be set arbitrarily.
The input and output of this transducer are completely isolated;  With the characteristics of high precision, high isolation and low thermal drift,this transducer is mainly used for the safety protection of various electrical control systems and other necessary protection devices.

 
This product features:
 
1. The input port and power port can withstand the surge impact of 4KV; It has the features of strong anti-jamming ability, safety and reliability.
 
2. It has relay passive contacts, OC gates and other output modes, making the product more widely used in a variety of security protection systems.
 
3. There are two types of installation, Standard 35mm DIN Rail and screw, which makes the installation simple and reliable.

Specification
 Test conditions: auxiliary power: +24V DC, room temperature: 25℃;
* Accuracy:Class 0.5
* Power Supply:12VDC, 24VDC (optional);
* Input Range:0.5A~30A AC (customizeable);
* Output:Switch value signal (Relay);
*  Alarm modes:Overcurrent alarming or undercurrent alarming. (customizable)
* Output Threshhold:2%-100%;  (customizeable)
* Backlash:1%-20%;(customizeable)
* Operating Temperature:-10℃~+60℃
* Static Power Consumption:≤1W
* Rated Power Consumption:≤1W
* Withstand Isolation Voltage:2500V DC;
* Response Time:≤300ms (default 265ms);
* Thermal Drift:≤300PPm/℃
* Lightning Surge Immunity:Power-supply end 2000V
* Case Style:E;
* Case Material:ABS ( Flame retardant)
* Mounting:35mm DIN rail or screw.


Wiring diagram

0.5A~30A AC, Three Phase AC Current Off-limit Alarm Transducer(图1)

Note:Current hole-thru input; Terminal 7,8,and 9 are for output. Terminal 7 is Nomal open, terminal 8 is Common, and Terminal 9 is Normal Close.  Terminal 10 and 11 are for power supply.



 