This transducer GS-AI1B1-xxPC(D) is a split core single Phase AC current transducer,adopting electromagnetic principle and open-close mode,easily achieving current measurement. Its input, output,and power supply are isolated from each other. This transducer has excellent linearity between input and output and can convert the input signal into a linear standard DC signal. This clamp type transducers are widely used in communications, electricity, railways, and real-time current signal detection or monitoring of industrial control and other fields;

contact us
share to:
  • Features
  • Download

Split core Single Phase AC Current Transducer GS-AI1B1-xxPC(D)


This transducer GS-AI1B1-xxPC(D) is a split core single Phase AC current transducer,adopting electromagnetic principle and open-close mode,easily achieving current measurement. Its input, output,and power supply are isolated from each other. This transducer has excellent linearity between input and output and can convert the input signal into a linear standard DC signal. This clamp type transducers are widely used in communications, electricity, railways, and real-time current signal detection or monitoring of industrial control and other fields;

Specifications:
❖ Test conditions:Power supply:+24V DC, room temperature:25℃,
❖ Accuracy:Class Class 0.5 or 1.0
❖ Input range: 0-20A~500A AC (0.5 class);
0-5A~20A AC (1.0 class)
❖ Output:0-5V/1-5V/0-20mA/4-20mA ,0-5KHz,0-10KHz;
❖ Power supply:+12V DC,15V DC,24V DC; ❖ Frequency:40-75Hz (can be to 5KHz; please specify when ordering)
❖ Load capacity:voltage output load ≥2KΩ,current output load ≤250Ω;
❖ Linear range:0-120%
❖ Isolation Voltage:≥2500V DC;
❖ Operating Temperature:-10℃~+60℃,Humidity:≤95% (no dew);
❖ Load of Output:Voltage Output ≥2KΩ;Current Output≤250Ω
❖ Rated Power:≤0.4W;
❖ Quiescent current:≤10mA;
❖ Output ripple:≤10mV;
❖ Surge Impact Immunity:
Power port three–level 2000V (L-N/2Ω/integrated wave);
Analog I/O port two-level 2000V (L-N/40Ω/integrated wave);
❖ Response Time:≤300ms;
❖ Thermal Drift:≤400PPm/℃;
❖ Input overload capacity: 20 times of the measured current nominal value(Maximum 500A)(Apply one second repeat 5 times, interval 300S)
❖ Storage condition: Temperature: -55~65℃; Humidity:≤95% (no dew);
❖ MTBF:greater than 100K hours; ❖ Case Material: ABS Flame retardant (UL94-V0);
❖ Installation:35mm DIN Rail.

 
Dimention
❖ Length:100mm;
❖ Width:36mm;
❖ Height:83mm;
❖ Window Diameter:φ31mm;


Application:
❖ Motor monitoring and controlling;
❖ Industrial automation monitoring System.
❖ Electricity grid monitoring system;
❖ Many other fields that the current should be monitored.
❖ Connecting to PLC;


 