DC Power Transducer

  • 5A~600A DC,50mV~1000V DC, DC Power Transducer
  • 5A~600A DC,50mV~1000V DC, DC Power Transducer
  • 5A~600A DC,50mV~1000V DC, DC Power Transducer
  • 5A~600A DC,50mV~1000V DC, DC Power Transducer

5A~600A DC,50mV~1000V DC, DC Power Transducer

contact us
share to:
  • Features
  • Download

DC Power Transducer measuring voltage 50mV-1000V DC,current 5A-600A DC.


     GS-DP1B0-xxKD series is  an electrically-isolated DC power transducer.It measures the power parameters in the electrical system and converts it to an industrial standard output signal that is proportional to the measured input.The output signal can be 0-5V DC,0-10V DC,0-20mA DC,4-20mA DC,2.5±2.5V DC,3±2V DC,10±10mA DC,12±8mA DC etc.Processing by the advanced MCU and precisive 24-digit AD Converter inbuilt,this transducer has the advantages of high precision and superior performance; It can be connected to PLC or other data acquisition system for the purpose of industrial monitoring and control.The input range is:voltage 50mV-1000V DC,current 5A-600A DC.
 
Specifications:
* Accuracy:Class 1.0;
* Power Supply:12VDC,24V DC,85~265V AC/DC;(Optional)
* Frequency:40~75Hz
* Input:Voltage:50mV~1000V DC;Current:5A~600A DC;(Customizable);
* Voltage Resistance:≥1KΩ*V;
* Output:0~5V, 0~10V,1~5V,0~20mA,4~20mA,2.5±2.5V,3±2V,10±10mA,
12±8mA DC;(Optional)
* Operating Temperature:-10℃~+60℃
* Load Capacity:Voltage output≥2KΩ;Current output≤250Ω;
* Rated Power Consumption:≤1W;
* Withstand Isolation Voltage:DC 2500V
* Response Time:≤300ms
* Thermal Drift:≤300PPm/℃
* Lightning Surge Immunity:Power-suply end 2000V,Input end 2000V, Output end 500V
* Case Style:K
* Case Material:ABS (flame retardancy, UL94-V0)
* Mounting:35mm DIN rail or Screw.

Wiring diagram

Single Phase AC Active Power (Watt) Transducer(图1)

Terminal 1 and 3 for voltage input; Current inputh thru aperture; Terminal 8 for output, terminal 10 and 11 for power supply; Terminal 12 for GND;

Oline Message